Vibration amplitudes in the Inuvik powerhouse

Vibration measurements in the main powerhouse at Inuvik, NWT, were taken to determine the amplitudes of vibration present in a structure supported on pile foundations in permafrost and subjected to large dynamic periodic forces. Accelerometers were placed on the support system for the main diesel ge...

Full description

Bibliographic Details
Main Authors: Pernica, G., Parameswaran, V. R., Johnston, G. H.
Format: Article in Journal/Newspaper
Language:English
Published: National Research Council of Canada 1985
Subjects:
sol
Online Access:https://nrc-publications.canada.ca/eng/view/ft/?id=ec7f1664-c194-4dc6-bc1a-ec915c5419ad
https://nrc-publications.canada.ca/eng/view/object/?id=ec7f1664-c194-4dc6-bc1a-ec915c5419ad
https://nrc-publications.canada.ca/fra/voir/objet/?id=ec7f1664-c194-4dc6-bc1a-ec915c5419ad
Description
Summary:Vibration measurements in the main powerhouse at Inuvik, NWT, were taken to determine the amplitudes of vibration present in a structure supported on pile foundations in permafrost and subjected to large dynamic periodic forces. Accelerometers were placed on the support system for the main diesel generator and on the floor and pile foundation of the one-storey industrial building. One-third octave band RMS acceleration amplitudes produced by the generator, a 5.2 MW system, are presented. In comparison to ambient acceleration amplitudes (generator off), amplitudes produced by the generator were approximately 430 times larger on the structural system supporting the generator and five to ten times larger throughout the remainder of the powerhouse. Les mesures effectuées dans la centrale électrique d'Inuvik, Territoires du Nort-Quest, ont permi de déterminer les amplitudes des vibrations dans la structure fondée sur pieux dans le pergélisol et sujette a des forces dynamiques périodiques. Des accéléromètres ont été placés sur le support du générateur diesel principal et sur le plancher ainsi que sur la fondation en pieux du Bâtiment industriel d'un étage. Le document rapporte les amplitudes de l'accélération (EMQ) d'une bande de fréquences d'un tiers d'octave produite par le générateur de 5.2 MW. Par comparaison aux amplitudes des accélérations locales (lorsque le générateur est arrêté), les amplitudes produites par le générateur et environ 5 à 10 fois plus importantes dans le reste de la centrale. Peer reviewed: No NRC publication: Yes