An Investigation of Ant-Nest Corrosion caused by the Leakage of a Copper Tube – Finned Heat Exchanger of an Air Conditioning Unit

Abstract Leakages often occur in the copper tube – finned heat exchangers of cooling and air conditioning units, the dimensions of which are on the microscopic scale thus making the location and cause very difficult to determine. In the case presented here the leakages found were located using a Hel...

Full description

Bibliographic Details
Published in:Practical Metallography
Main Authors: Gaedicke, R., Stein, S.
Format: Article in Journal/Newspaper
Language:English
Published: Walter de Gruyter GmbH 2015
Subjects:
Online Access:http://dx.doi.org/10.3139/147.110321
https://www.degruyter.com/view/journals/pm/52/12/article-p736.xml
https://www.degruyter.com/document/doi/10.3139/147.110321/xml
https://www.degruyter.com/document/doi/10.3139/147.110321/pdf
Description
Summary:Abstract Leakages often occur in the copper tube – finned heat exchangers of cooling and air conditioning units, the dimensions of which are on the microscopic scale thus making the location and cause very difficult to determine. In the case presented here the leakages found were located using a Helium leak detector. After removing the fins of the heat exchanger, because the points of failure were not visible to the naked eye, a dye penetrant test was carried out on the affected area (Penetrations test or PT), which led to the discovery of three very small indications on one section of the tube. Subsequent microscopic laboratory examination revealed the cause to be microscopically small holes in the wall of the tube caused by corrosion through from the internal surface of the coolant side of the tube. The corrosion mechanism was identified as Formicary Corrosion otherwise referred to as Ant-Nest Corrosion. For this type of corrosion to occur, which according to the specialist literature is often found in Cooling or Air Conditioning units, an aqueous electrolyte or electrolytic film containing Carbonic acid and Oxygen is required which can lead to damage occurring within weeks to months. In the case described in this article, the unintentional ingress of an aqueous oxygenated acidic solution of Glycol into the heat exchanger was most probably responsible for the damage.