Case study of offshore wind farm integration to offshore oil and gas platforms as an isolated system - System Topologies, Steady State and Dynamic Aspects

The objective of this thesis work has been to investigate the electric system stability, reliability and power security of an off-grid isolated network system integration of an offshore wind farm to offshore oil and gas platforms via HVAC transmission, considering different network topologies for wi...

Full description

Bibliographic Details
Main Author: Hadiya, Maheshkumar
Other Authors: Uhlen, Kjetil, Norges teknisk-naturvitenskapelige universitet, Fakultet for informasjonsteknologi, matematikk og elektroteknikk, Institutt for elkraftteknikk
Format: Master Thesis
Language:English
Published: Institutt for elkraftteknikk 2011
Subjects:
Online Access:http://hdl.handle.net/11250/257145
id ftntnutrondheimi:oai:ntnuopen.ntnu.no:11250/257145
record_format openpolar
institution Open Polar
collection NTNU Open Archive (Norwegian University of Science and Technology)
op_collection_id ftntnutrondheimi
language English
topic ntnudaim:6066
MSELPOWER Master of Science in Electric Power Engineering
spellingShingle ntnudaim:6066
MSELPOWER Master of Science in Electric Power Engineering
Hadiya, Maheshkumar
Case study of offshore wind farm integration to offshore oil and gas platforms as an isolated system - System Topologies, Steady State and Dynamic Aspects
topic_facet ntnudaim:6066
MSELPOWER Master of Science in Electric Power Engineering
description The objective of this thesis work has been to investigate the electric system stability, reliability and power security of an off-grid isolated network system integration of an offshore wind farm to offshore oil and gas platforms via HVAC transmission, considering different network topologies for wind power penetration, network losses, application of FACTS devices and different system voltage levels. The system stability studies were performed by steady state and dynamic simulations, analysing different perturbation events in the system. The power system model under study was established as a continuation of a previous work concerning a single platform system. The model can be seen to represent the Oseberg oilfield in the Norwegian Sea consisting of five offshore platforms. The complete model represents a grid integration of the five offshore platforms with a total load demand of 147MW to an offshore wind farm of 100MW production via HVAC as an isolated system. Wind farm capacity is less but of comparable size to the total load. Each platform has its own offshore power generation units (Gas Turbines - GTs) to cover the load demand at each platform. Load demands were selected based on recently collected real operational power consumption data from Statoil, ASA. In this study, 8 GTs were installed at different specific platforms to cope with the load of 150MW. Three different network topology configurations were considered, denoted Star, Star-F and Meshed. Four types of perturbation/disturbance events were analysed: Starting of 9MW asynchronous motor at Platform4, loss of a GT at Platform4, sudden loss of wind power production and loss of interconnection cable between Platform1 and Plaform4. The dynamic system stability was assessed by measuring frequency and voltage deviations at specific load buses to ensure whether transient deviations were following offshore NORSOK or IEC standards correctly or not. For each type of disturbances, different topology aspects were considered and analysed for different outages and different cases of percentage of wind power penetration. It could be seen that generators at platforms in all cases were able to regain synchronism by maintaining terminal voltage and power factor within allowed ranges after disturbances caused by Starting of 9MW motor, loss of wind power, loss of a GT and loss of cable. This can be explained because the isolated network system has a strong spinning reserve capacity. But not all studied scenarios were dynamically stable, following NORSOK standards for transient of voltage and frequency variations. The results showed the importance of an integrated grid system: Starting of big induction motor was found not to give large frequency or voltage deviations compared to the previous study of a single platform system since the integrated system has a larger inertia. Voltage deviations were found most critical in case of starting big motors. In addition, a meshed topology have better performace with less voltage and frequency deviation compared to the other two topologies for all perterbation events and cases. The results also showed that loss of wind power was more critical at high wind power penetration levels. A 100% sudden loss of wind power gave unacceptable frequency deviations. The study of two different voltage levels, 36kV and 52kV showed that a 52 kV network gave better dynamic stability behaviour compared to the other one. The study of FACTS devices applications showed that a STATCOM was more efficient in dynamic control of voltage than an SVC due to its better reactive power compensation capability at lower voltage, thus improving power transmission capability for the same power ratings.
author2 Uhlen, Kjetil
Norges teknisk-naturvitenskapelige universitet, Fakultet for informasjonsteknologi, matematikk og elektroteknikk, Institutt for elkraftteknikk
format Master Thesis
author Hadiya, Maheshkumar
author_facet Hadiya, Maheshkumar
author_sort Hadiya, Maheshkumar
title Case study of offshore wind farm integration to offshore oil and gas platforms as an isolated system - System Topologies, Steady State and Dynamic Aspects
title_short Case study of offshore wind farm integration to offshore oil and gas platforms as an isolated system - System Topologies, Steady State and Dynamic Aspects
title_full Case study of offshore wind farm integration to offshore oil and gas platforms as an isolated system - System Topologies, Steady State and Dynamic Aspects
title_fullStr Case study of offshore wind farm integration to offshore oil and gas platforms as an isolated system - System Topologies, Steady State and Dynamic Aspects
title_full_unstemmed Case study of offshore wind farm integration to offshore oil and gas platforms as an isolated system - System Topologies, Steady State and Dynamic Aspects
title_sort case study of offshore wind farm integration to offshore oil and gas platforms as an isolated system - system topologies, steady state and dynamic aspects
publisher Institutt for elkraftteknikk
publishDate 2011
url http://hdl.handle.net/11250/257145
geographic Norwegian Sea
geographic_facet Norwegian Sea
genre Norwegian Sea
genre_facet Norwegian Sea
op_source 137
op_relation 447297
ntnudaim:6066
http://hdl.handle.net/11250/257145
_version_ 1766151504871292928
spelling ftntnutrondheimi:oai:ntnuopen.ntnu.no:11250/257145 2023-05-15T17:47:09+02:00 Case study of offshore wind farm integration to offshore oil and gas platforms as an isolated system - System Topologies, Steady State and Dynamic Aspects Hadiya, Maheshkumar Uhlen, Kjetil Norges teknisk-naturvitenskapelige universitet, Fakultet for informasjonsteknologi, matematikk og elektroteknikk, Institutt for elkraftteknikk 2011 http://hdl.handle.net/11250/257145 eng eng Institutt for elkraftteknikk 447297 ntnudaim:6066 http://hdl.handle.net/11250/257145 137 ntnudaim:6066 MSELPOWER Master of Science in Electric Power Engineering Master thesis 2011 ftntnutrondheimi 2019-09-17T06:49:38Z The objective of this thesis work has been to investigate the electric system stability, reliability and power security of an off-grid isolated network system integration of an offshore wind farm to offshore oil and gas platforms via HVAC transmission, considering different network topologies for wind power penetration, network losses, application of FACTS devices and different system voltage levels. The system stability studies were performed by steady state and dynamic simulations, analysing different perturbation events in the system. The power system model under study was established as a continuation of a previous work concerning a single platform system. The model can be seen to represent the Oseberg oilfield in the Norwegian Sea consisting of five offshore platforms. The complete model represents a grid integration of the five offshore platforms with a total load demand of 147MW to an offshore wind farm of 100MW production via HVAC as an isolated system. Wind farm capacity is less but of comparable size to the total load. Each platform has its own offshore power generation units (Gas Turbines - GTs) to cover the load demand at each platform. Load demands were selected based on recently collected real operational power consumption data from Statoil, ASA. In this study, 8 GTs were installed at different specific platforms to cope with the load of 150MW. Three different network topology configurations were considered, denoted Star, Star-F and Meshed. Four types of perturbation/disturbance events were analysed: Starting of 9MW asynchronous motor at Platform4, loss of a GT at Platform4, sudden loss of wind power production and loss of interconnection cable between Platform1 and Plaform4. The dynamic system stability was assessed by measuring frequency and voltage deviations at specific load buses to ensure whether transient deviations were following offshore NORSOK or IEC standards correctly or not. For each type of disturbances, different topology aspects were considered and analysed for different outages and different cases of percentage of wind power penetration. It could be seen that generators at platforms in all cases were able to regain synchronism by maintaining terminal voltage and power factor within allowed ranges after disturbances caused by Starting of 9MW motor, loss of wind power, loss of a GT and loss of cable. This can be explained because the isolated network system has a strong spinning reserve capacity. But not all studied scenarios were dynamically stable, following NORSOK standards for transient of voltage and frequency variations. The results showed the importance of an integrated grid system: Starting of big induction motor was found not to give large frequency or voltage deviations compared to the previous study of a single platform system since the integrated system has a larger inertia. Voltage deviations were found most critical in case of starting big motors. In addition, a meshed topology have better performace with less voltage and frequency deviation compared to the other two topologies for all perterbation events and cases. The results also showed that loss of wind power was more critical at high wind power penetration levels. A 100% sudden loss of wind power gave unacceptable frequency deviations. The study of two different voltage levels, 36kV and 52kV showed that a 52 kV network gave better dynamic stability behaviour compared to the other one. The study of FACTS devices applications showed that a STATCOM was more efficient in dynamic control of voltage than an SVC due to its better reactive power compensation capability at lower voltage, thus improving power transmission capability for the same power ratings. Master Thesis Norwegian Sea NTNU Open Archive (Norwegian University of Science and Technology) Norwegian Sea